Customization: | Available |
---|---|
Type: | Power Source Arrester |
Application: | AC/DC System |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. AC surge protective device for low-voltage power system Characteristic
-Class I+II / Type 1+2 SPD Iimp 12kA.
-For using in the lightning protection zones concept at boundary 1-2.
-The core parts are metal oxide vristor components with high discharge capacity.
-Low residual voltage and quick response
-Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
-Protection mode: L-N, N-PE.
2. AC surge protective device for low-voltage power system Dimension and Circuit FV40B+C/1+NPE-275(S)
Model No.: FV40B+C/1+NPE-275(s) | |||
Max. continuous AC voltage | Uc | V | 275 |
Requirement class to DIN EN 61643-1: 2005 | Class B+C | ||
Nominal Discharge current(8/20μ s) | In | kA | 40 |
Max. discharge current (8/20μ s) | Imax | kA | 80 |
Voltage protection level (at In) | Up | kV | <=1.7 |
Response time | tA | ns | 25 |
Operation temperature range | -40 ~ +85degree | ||
Degree of protection | IP20 | ||
Remote control contacts | optional |