AC SPD FVC20C/1+NPE-385S is for low-voltage power supply 385V, Imax 40kA, 2poles.
1.surge protective device Characteristic for FVC20C/1+NPE-385S
-Special design for saving installation space --- width 9mm/pole.
-High discharge current --- Imax 40kA per pole.
-Indication window for clear display of SPD status --- each pole with one indication window.
-Pluggable module --- convenient for maintenance.
-Protection mode --- L-N, N-PE
-equivalent to CITEL DS240-230/G
2. FVC20C/1+NPE-385S surge protective device are suitable for lightning and surge protection in AC 50/60Hz, 220/380V.
3. APPLICATION of surge protective device FVC20C/1+NPE-385S:
AC power line of house, bank, telecom tower and so on.
4. Dimension, circuit and installation of surge protective device FVC20C/1+NPE-385S
WHY CHOOSE US
FATECH ELECTRONIC CO., LTD., is located in Guangdong Provincial New Light Production Base, CHINA, which is a professional manufacturer on R&D and producing on surge protection products. Our company gathered all kinds of high-skillled personnels, including authority technical experts and professionals, and excellent technicians with more than 10 years experience. In-house testing lab. guarantee out-going products quality. Products are certified with TUV, CE; UL pending, 90% material are UL approved.
Our in-house test lab.:We established an independent testing laboratory, including reliability testing laboratory, environmental aging testing laboratory, release testing laboratory, which can be performed tests below:
- Impulse current generator (8/20 μS/160kA and 10/350μS/20kA)
- Thermal stability tester
- Salt Spray Chamber
- Multi-function Varistor Tester
- On-line Aging Tester
- Dielectric Voltage Withstand Tester
- 1.2/50 Voltage Impulse Generator
- Environment Stimulating Tester
- Lightning Surge Counter Tester
Our global partners:
We are now exporting more than 100 countries and areas, mainly in Europe, Asia, Latin-America, and Middle East. Our global partner including
- Ericsson
- Sri Lanka Telecom
- Siemens
Our certificates:
We also can supply more of product for low--voltage power system lightning arrester , surge protective device with Imax=60kA, 100kA. And type B spd with spark gap.
If you are interested in ,please feel free contact to me!
Model No.: FVC20C/1+NPE-385S |
|
|
|
Max. continuous AC voltage |
Uc |
V |
385 |
Requirement class to DIN EN 61643-1: 2005 |
|
|
Class C |
Nominal Discharge current(8/20μ s) |
In |
kA |
20 |
Max. discharge current (8/20μ s) |
Imax |
kA |
40 |
Voltage protection level (at In) |
Up |
kV |
<=1.8 |
Response time |
tA |
ns |
25 |
Operation temperature range |
|
|
-40 ~ +85degree |
Degree of protection |
|
|
IP20 |
Remote control contacts |
|
|
YES |