Customization: | Available |
---|---|
Type: | Power Source Arrester |
Application: | AC/DC System |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model No. | FV30B+C/4- 150(S) |
FV30B+C/4- 275(S) |
FV30B+C/4- 320(S) |
|||
Rated Voltage | UN | VAC | 120 | 230 | 230 | |
Max. continuous. operating voltage | UC | VAC | 150 | 275 | 320 | |
Nominal discharge current(8/20μs) | In | kA | 30 | 30 | 30 | |
Max. discharge current (8/20μs) | Imax | kA | 60 | 60 | 60 | |
Iimpulse discharge current (10/350μs) | Iimp | kA | 7 | 7 | 7 | |
Voltage protection level (at In) | Up | kV | ≤0.9 | ≤1.5 | ≤1.8 | |
Response time | tA | ns | <25 | <25 | <25 | |
Recommended back-up fuse | A | 160 | 160 | 160 | ||
I/O Connections | By screw terminal:10-35mm2; By connection bus | |||||
Mounting | Symmetrical rail(EN50022/DIN46277-3) | |||||
Operation temperature range | -40ºC~+85ºC | |||||
Degree of protection | IP20 | |||||
Housing material | UL94V0 | |||||
Disconnection indicator | Mechanical indicator | |||||
Remote control contact | Optional |