Model No.: FV30B+C/2-275 (S) | |||
Max. continuous AC voltage | Uc | V | 275 |
Requirement class to DIN EN 61643-1: 2005 | Class B+C | ||
Nominal Discharge current(8/20μ s) | In | kA | 30 |
Max. discharge current (8/20μ s) | Imax | kA | 60 |
Impuse discharge current (10/350μs) | Iimp | kA | 7 |
Voltage protection level (at In) | Up | kV | <=1.5 |
Response time | tA | ns | 25 |
Recommended back-up fuse | A | 160 | |
Operation temperature range | -40 ~ +85degree | ||
Degree of protection | IP20 | ||
Remote control contacts | optional |