SPD FV10D/1-275(S) is for low-voltage power supply 275V, Imax 20kA, 1pole.
1. Surge protection device for low-voltage power system Characteristic FV10D/1-275(S)
-Class II / Type 2 surge protector.
-Consisting of a base part and1 MOV plug-in protection modules.
-For using in the lightning protection zones concept at boundary 1-2.
-The core parts are metal oxide vristor components with high discharge capacity.
-Low residual voltage and quick response
-Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
-Protection mode: L/N-PE.
2. FV10D/1-275(S)surge protection device are suitable for lightning and surge protection in AC 50/60Hz, 220/380V.
3. APPLICATION of surge protection device FV10D/1-275(S):
AC power line of house, bank, telecom tower and so on.
4. Surge protection device for low-voltage power system Certificate:
CE-LVD
We also can supply more of product for low--voltage power system lightning protective device, surge protective device with Imax=80kA, 100kA. And type B SPD with spark gap.
If you are interested in, please feel free contact to me!
Model No.: FV10D/1-275(S) |
|
|
|
Max. continuous AC voltage |
Uc |
V |
275 |
Requirement class to DIN EN 61643-1: 2005 |
|
|
Class D |
Nominal Discharge current(8/20μ s) |
In |
kA |
10 |
Max. discharge current (8/20μ s) |
Imax |
kA |
20 |
Voltage protection level (at In) |
Up |
kV |
<=1.2 |
Response time |
tA |
ns |
25 |
Operation temperature range |
|
|
-40 ~ +85degree |
Degree of protection |
|
|
IP20 |
Remote control contacts |
|
|
optional |