1 pole - AC surge protective device, DIN rail mount replaceable surge modules with 1 MOV Imax 100kA.
FV50C/1-***(s) 1 phase AC power Surge Protection Device are suitable for lightning and surge protection in AC 50/60Hz, 220/380V.
Features of Surge Protective Device FV50C/1-***(s):
There is a thermal cutoff member inside the power Lightning Protection Device, when the device is over-current or over-voltage and the puncture is nonseviceable, the thermal cutoff member will automatically separate from the power Lightning Protection Device from the electrical network, and the indication window will turn red from green.
APPLICATION of Surge Protective Device FV50C/1-***(s)
AC power line of house, bank, telecom tower and so on.
Certificate of Surge Protective Device FV50C/1-***(s):
CE-LVD
We also can supply DC Lightning Protection Device for photovoltaic (PV) system protection 1000VDC, surge protective device with Imax=60KA, 150KA. And type B surge arrester with spark gap.
Model No. | | | FV50C/1-275S | FV50C/1-320S | FV50C/1-385S | FV50C/1-440S |
Max. continuous operating voltage | Uc | V | 275 | 320 | 385 | 440 |
Requirement class to DIN EN 61643-1:2005 | | | Class C | Class C | Class C | Class C |
Rated Voltage | Un | V | 220/380 | 220/380 | 220/380 | 220/380 |
Nominal discharge current (8/20μs) | In | kA | 50 | 50 | 50 | 50 |
Max. discharge current (8/20μs) | Imax | kA | 100 | 100 | 100 | 100 |
Voltage protection level (at In) | Up | kV | ≤ 1.8 | ≤2.2 | ≤ 2.5 | ≤ 2.8 |
Response time | tA | ns | <25 | <25 | <25 | <25 |
Recommended back-up fuse | | A | 125 | 125 | 125 | 125 |
Operation temperature range | | | -40 ~+85 | -40 ~+85 | -40 ~+85 | -40 ~+85 |
Degree of protection | | | IP20 | IP20 | IP20 | IP20 |