Three phase 4 poles surge arrestor, DIN rail mount replaceable surge modules with 4MOV module Imax 40kA/P.
FV20C/4 surge arrestor are suitable for lightning and surge protection in AC 50/60Hz, 220/380V.
Features of the 4P surge arrestor FV20C/4-***(S):
:
There is a thermal cutoff member inside the surge arrestor, when the device is over-current or over-voltage and the puncture is nonseviceable, the thermal cutoff member will automatically separate from the surge arrestor from the electrical network, and the indication window will turn red from green.
Codeing
APPLICATION of surge arrestor FV20C/4-***(S):
AC power line of house, bank, telecom tower and so on.
Certificate of the surge arrestor FV20C/4-***(S):
CE-LVD
We also can supply DC surge arrestor for photovoltaic (PV) system protection 1000VDC, surge arrestor with Imax=60KA, 150KA. And type B surge arrester with spark gap.
Model No. |
FV20C/4-275S |
FV20C/4-320S |
FV20C/4-385S |
FV20C/4-440S |
Max. continuous operating voltage |
Uc |
V |
275 |
320 |
385 |
440 |
Requirement class to DIN EN 61643-1:2005 |
|
|
Class C |
Class C |
Class C |
Class C |
Rated Voltage |
Un |
V |
220/380 |
220/380 |
220/380 |
220/380 |
Nominal discharge current (8/20μs) |
In |
kA |
20 |
20 |
20 |
20 |
Max. discharge current (8/20μs) |
Imax |
kA |
40 |
40 |
40 |
40 |
Voltage protection level (at In) |
Up |
kV |
≤1.2 |
≤1.5 |
≤1.8 |
≤2.0 |
Response time |
tA |
ns |
<25 |
<25 |
<25 |
<25 |
Recommended back-up fuse |
|
A |
125 |
125 |
125 |
125 |
Operation temperature range |
|
|
-40~+85 |
-40~+85 |
-40~+85 |
-40~+85 |
Degree of protection |
|
|
IP20 |
IP20 |
IP20 |
IP20 |